To prevent data loss and corruption, Suffield has several Uniterruptable Power Supplies (UPSes) that provide battery-backed power in the event of an electrical outage.
Most of our UPSes have a serial port, which allows a computer running monitoring software to receive status updates from the unit. This way, the host can shut down when the batteries of the unit run low.
Because each of our UPSes have more than one server attached to them, we needed a centralized way to manage the UPSes and shut down all affected servers during an outage. We settled on a software package called NUT, which stands for Network UPS Tools.
The software is easy to compile for UNIX-based operating systems, and there is also a Windows client available. NUT provides monitoring, reporting, alerts, and a client-server model that allows for very complex setups involving multiple servers and UPSes.
At Suffield Academy, we have a single centralized host that acts as the master server for UPS information. It has a multi-port serial card, and all UPS units are attached directly to it. All other hosts connect to this server via the network and poll it for UPS status information.
This centralized setup allows us to easily add new servers to our power configuration. We simply add client software to the machine and configure it to poll a particular UPS instance on the server. The server automatically broadcasts power outage events to the clients, which shut themselves down before the batteries are completely drained.
Suffield uses a setup where all the UPS units are connected to a single centralized server. This section deals with setting up such a centralized system, though it is relatively straightforward to adapt it to a multiple-master configuration as well.
Get and install the nut
package. This means compiling it from
source, or downloading a version through your distribution's packaging
system. Note that some package systems break NUT up into several
pieces (e.g., drivers, client, and server), so you may need to
install more than one package.
Under Debian Linux (our platform of choice), this ought to do it:
apt-get install nut
The first step is to get a list of the port devices on your server,
and figure out which ones go with which UPS. For example, if you've
plugged a UPS into serial port 1, it might be connected on
/dev/ttyS0
under Linux. If you have multiple serial ports
(perhaps through an add-on board or other interface), you'll need to
come up with a mapping of all the device names to the ports they use.
We highly recommend labelling the ports externally so that you may easily verify their device assignments.
You must change the permissions on all ports so they are accessible by
the daemon running NUT. Under Debian, the files should be owned to
user nut
and group nut
. Additionally, make sure no other
users have write access to the device:
sudo chown nut:nut /dev/<device node> sudo chmod 660 /dev/<device node>
Begin by editing the ups.conf
file. This file defines all the UPS
hardware that is directly connected to this machine.
For each UPS, you must specify the following:
sdorder
)
sdtype
-- certain models only)
The sdorder
flag allows certain UPSes to be powered down before
others. Use this to enforce an ordering on the powerdown sequence
(lower numbers are powered down before higher numbers; -1 excludes
from the sequence entirely).
The sdtype
is special to the apcsmart
driver (which we use
with our APC UPSes). It determines the shutdown command to send to
the UPS (e.g., power off but don't restart automatically, power
off now, power off with delay).
A sample stanza might look like:
[nicole] driver = apcsmart port = /dev/ttyS0 # Set load to turn back on automatically when power returns sdtype = 0 desc = "Smart-UPS 1000" sdorder = 10
Note: we name our UPS hardware after bratty spoiled people (the "SSW" naming scheme), which is why you'll see several women's names in our sample configs.
Once you've defined the hardware attached to the machine, you must now
specify who has access to the hardware (via the upsd
daemon).
Begin by editing the upsd.conf
file. This file allows you to
specify ACL statements defining network hosts (or blocks).
You must add two lines for each host or netblock you wish grant access to. The first defines the host/netblock with a name, and the second grants (or revokes) access. Any configuration should include entries for the local machine, and a default deny:
# Define blocks ACL localhost 127.0.0.1/32 ACL all 0.0.0.0/0 ACL myservers 172.16.0.0/12 # Grant or revoke access (deny by default) ACCEPT localhost ACCEPT myservers REJECT all
Finer-grained control of who can log in from where is possible by combining ACLs with user-based permissions (see next section).
You may further restrict who has access to which UPS (and what they can do with it) by specifying users. In our case, the "division of labor" is quite clear-cut (a server which controls all the hardware, and numerous clients that may only poll for status). Thus, we only need a few users: one with full control, one that can monitor and take action on all UPSes, and one that can only monitor.
If your setup is more complex, you may need additional users. Additionally, you may wish to create individual users for particular machines for finer-grained control.
Here's a sample minimum configuration:
# Local user with full manual control over all UPSes [superuser] password = supersecret allowfrom = localhost actions = SET FSD instcmds = all # upsmon agent user with full control over all UPSes # (used for local monitoring agent on master server) [masteruser] password = secret allowfrom = localhost upsmon master # upsmon agent with read-only privs # (used for remote monitoring agents on other machines) [slaveuser] password = kindasecret allowfrom = localhost myservers upsmon slave
The server is now configured to "listen" to several pieces of UPS hardware. We must now specify which UPSes this machine will monitor and interact with, so that we can automatically shut down machines, send pages and e-mails, and take other actions.
We do this by editing the upsmon.conf
file. This file is quite
large, so we'll take several steps to make all the edits necessary.
You must specify the UPSes you wish to monitor. Since we have a "one central server" approach, we add monitoring lines for all UPSes attached to the machine.
The central server should be allowed to interact with the UPS hardware (i.e., turn it off and on), so we use our "master monitor" name and password for each UPS.
MONITOR nicole@localhost 1 masteruser secret master MONITOR paris@localhost 1 masteruser secret master
Note that each MONITOR
line must have a "power value" associated
with it, specifying how many outlets on the current machine are
powered by this UPS. Unfortunately, setting the power value to 0
means that the system will not automatically report status on the
UPS. Thus, for a central master system, you'll need to assign a
positive integer for every UPS that you're managing.
This complicates things a little, as now you have a machine that appears to be powered by many UPSes. The remedy is as follows:
MINSUPPLIES
value to this high value.
The net effect is that the UPSes connected to the server will be "weighted" to count more than the other UPSes. This way, the system won't actually initiate a shutdown until it's lost the UPSes that are cruicial to its operation, but will still process events from the other UPSes.
NUT has the ability to run an external program whenever an event is
received from a UPS. To make this as flexible as possible, NUT
includes a binary called upssched
which processes events from the
UPS and fires off a script of your choosing when they occur.
It's a little complicated because of this extra binary, but it works well and is quite flexible.
Begin by editing upsmon.conf
and adding an entry for
NOTIFYCMD
. We use the built-in upssched
binary, as it
provides several useful features (like timers):
NOTIFYCMD /sbin/upssched
(Note that the location of the binary may be different on your system.)
Once you've done that, move down in the file and add entries for
NOTIFYFLAG
. We must tell upsmon
what to do with each event it
receives from a UPS; it can be any combination of the following:
NOTIFYCMD
We've opted to log all messages to syslog and execute upssched
:
NOTIFYFLAG ONLINE SYSLOG+EXEC NOTIFYFLAG ONBATT SYSLOG+EXEC NOTIFYFLAG LOWBATT SYSLOG+EXEC NOTIFYFLAG FSD SYSLOG+WALL+EXEC NOTIFYFLAG COMMOK SYSLOG+EXEC NOTIFYFLAG COMMBAD SYSLOG+EXEC NOTIFYFLAG SHUTDOWN SYSLOG+EXEC NOTIFYFLAG REPLBATT SYSLOG+EXEC NOTIFYFLAG NOCOMM SYSLOG+EXEC
Now, save your changes and edit the file upssched.conf
. This file
determins what upssched
does when it receives an event. At first,
the file seems a little limiting; you may only specify one script to
execute for all events. However, it provides one very important
feature which makes it worth it: timers.
upssched
has the ability to trigger a timer for any event, and
to cancel a timer that has not executed. For example, you could set a
30-second timer to send an e-mail when an UPS goes on battery, and
then cancel the timer when the UPS goes back on line power. This
gives you an easy way to "buffer" events before they get acted on,
which is very useful for power "blips" (e.g., outages lasting
fewer than 30 seconds).
Begin by declaring the command to execute for all events. We have
written our own script, called upssched-dispatch
(download it from our website),
which is written in Perl:
CMDSCRIPT /usr/local/bin/upssched-dispatch
You may need to specify values for PIPEFN
and LOCKFN
,
depending on your operating system layout and configuration defaults.
For example, on a Debian system you need the following:
PIPEFN /var/run/nut/upssched.pipe LOCKFN /var/run/nut/upssched.lock
Finally, you must specify the events you wish to act on. We do this
by specifying AT
commands in the config file. The general form
is:
AT <event> <upsname> <action> <arguments>
The event may be any UPS event (e.g., ONBATT
, COMMBAD
).
The upsname is the name@host identifier for the UPS. The action is
one of EXECUTE
, START-TIMER
, or CANCEL-TIMER
. The
arguments get passed to your command script.
You need to pick an arrangement of actions such that you're notified of all the events you want to hear about. See our configuration file for an example of how we've done it.
One important note: you may use *
in place of a particular UPS
name. However, if you do so with a timer, you may find that some
events get masked by others. If you're going to use timers, you
should set a specific timer for each individual UPS.
Now that NUT is configured, you're ready to turn it on. Under some systems, you may need to edit a file so NUT knows to officially launch and take over power management for your system.
Under Debian, you must edit the /etc/default/nut
file and enable
the UPSD and UPSMON subsystems.
Once you've done this, you can start the daemon, and check your syslog file to see if it's started properly. You should see status messages from all your UPSes.
NUT includes one final piece of functionality: the ability to report UPS status via a web interface. Most packaged versions of NUT include this functionality as a separate install, so it may not be included with the standard NUT daemon.
The CGI is simple to configure; enable it as you would any other CGI
(see your web server documentation for more info), and then add the
files hosts.conf
, upsstats.html
, upsstats-single.html
, and
upsset.html
to your configuration directory (you may omit
upsset.html
if you do not wish to allow editing UPS configurations
via the web).
The hosts.conf
file simply lists the UPSes you wish to make
available via the web interface.
The HTML files contain a template file that is used by the CGI to generate pages about all (or one) UPS(es). The default files show a reasonable amount of information, though you may wish to edit them to your taste (to display additional information, or to alter the formatting).
Precompiled versions of NUT exist for many free operating systems (such as Linux or the BSDs). If you use one of these operating systems, consult your package manager to see if a ready-made version is available.
We have compiled our own versions of the NUT software for the operating systems that we use at Suffield (see previous sections for downloads). Here is a brief guide for compiling from scratch, geared towards Mac OS X.
There are three major versions of NUT available as of this writing:
While the 1.4 and 2.0 series are protocol-compatible (i.e., a 1.4 client can talk to a 2.0 server), the configuration files and structure are not compatible. Thus, you should try to stick with the same major release across platforms. We currently use the stable 2.0 series.
Download the latest stable client from the NUT downloads page:
http://www.networkupstools.org/source.html
Unpack the distribution on your machine, and move into the top-level directory.
For security purposes, NUT prefers to run under its own username. You should create a local username on your machine using the standard account creation tools. The user should not have login access to the account, so disable logins via a bogus password or other account locks.
We use nut_upsmon
as the username for our custom installations.
In the top-level configuration directory, run the configure
script. You may wish to provide options to configure
to customize
its behavior; here are the options we use:
--prefix=/usr/local/nut_upsmon
, which locates all the installed
software to a single directory on the filesystem (makes for easier
packaging).
--with-statepath=/usr/local/nut_upsmon/state
, which tells NUT to
store driver information in the local software tree. Defaults to
/var/state
, but we move it to make it easier to track.
--with-user=nut_upsmon
, which is the user we created in the
previous step.
--with-drivers=apcsmart
, which reduces the drivers we
use. In reality, the clients probably won't need any drivers, as
they'll be querying our master server. We throw the drivers in "for
free" in case we need them (we only use APC model UPSes, so this is an
easy choice). You should include only the UPSes that your site uses.
Once the configure step is done, run make
to compile the software.
When make
is finished, you may install the software directly by
running make install
, or you may divert the install to another
directory for packaging. Since we build packages, we opt for the
latter:
make DESTDIR=/tmp/nut_upsmon install
You'll need to add configuration files to
/usr/local/nut_upsmon/etc/
for the clients. Because we run a
centralized server, the clients should not need any configuration
files dealing with the "server" parts of NUT. At a minimum, you'll
need an upsmon.conf
file (specifying a remote UPS to monitor), and
you may optionally want an upssched.conf
file if you wish to
perform additional tasks (such as early shutdowns).
Our setup involves three custom files, which you may download below:
upsmon.conf
(download),
which specifies a remote server to query for UPS state information.
upssched.conf
(download),
which specifies a special script (early-shutdown
; see below) to
execute when a UPS has been on battery for a certain amount of time.
This allows certain machines to be shutdown before the battery goes
critical.
early-shutdown
(download), which is a script that
receives events from upssched
and shuts the machine down early.
The software should be configured to run on boot. For UNIX-based systems, this probably involves editing the init scripts on the platform.
For Mac OS X, we prefer to use launchd
, which is Apple's new way
of automatically running software starting with 10.4. Unfortunately,
nut
doesn't play nice with launchd
by default, as it detaches
and forks from the controlling terminal.
We've written a simple wrapper script that sits between launchd
and upsmon
(the client part of nut
). It's called
upsmon_launchd_wrapper
, and you can
download it from our site.
You'll also need the
launchd plist file,
which should be placed in the /Library/LaunchDaemons
folder and
activated.
Ordinarily, the UPS will let you know when it thinks it's time to replace its battery. Most UPSes self-test on a regular basis, and if one of these tests shows that the battery isn't holding a proper charge, a REPLBATT message will be issued by NUT. Do not ignore these messages! Batteries that don't hold a charge may provide little (or no) runtime.
Order a replacement battery for the UPS. In the case of APC Smart-UPSes, the batteries can be swapped while the UPS is powered on. Simply unscrew the bezel, pull the large power connectors, and remove the old battery. Replace with the new battery and reverse the steps to close the UPS up.
APC UPSes have internal variables that allow you to keep track of when the battery was installed. Unfortunately, these variables are not set automatically, so you'll need to freshen them up when you add the new battery.
To do this, run the upsrw
command, and provide the date (you'll
need the master user password):
upsrw -s "battery.date=2007Apr1" -u upsmaster "myups@localhost"
We use a textual month to prevent ambiguity in date format.
Once the battery is installed, you'll need to let the UPS know that there's a new battery. APC recommends waiting at least 8 hours for the battery to get a full charge before you re-run the self test. Once 8 hours have elapsed, issue a self-test and the "replace battery" light should go out.
Unfortunately, this process isn't perfect, and sometimes the UPS will still think it needs a new battery. This can manifest in one of two ways:
If this happens, try the following until the situation is resolved:
Issue a self-test on the UPS, by holding in the test button (or starting the test from software). The "replace battery" light should go out after the test.
If the self-test doesn't seem to "take", you can perform a runtime calibration. You can start this by issuing an ups command:
upscmd -u upsmaster -p <password> myups@localhost calibrate.start
The calibration process must be started with the ups at a 100% charge! The calibration also must have a load attached (if you're nervous about production machines being attached, find a "dummy" load to run.
The process puts the UPS on battery, and drains the battery to 25% before automatically switching to line power. The UPS uses the load data and time to compute the new runtime estimate.
If a software calibration doesn't help, then a forced calibration may be necessary. The following are taken from the NUT FAQ (http://www.networkupstools.org/faq/) and also from phone instructions given by an APC technition.